Financing through Online Credit smart by BT Direct
How can we help you?
Description
Oil Burner Control Unit TF 974
The Honeywell Satronic TF974 Control Box is an automated burner controller for 1 or 2-stage oil power burners up to 30 kg/h capacity and intermittent operations.
FLAME DETECTION:
- Photoresistor MZ 770 S
- Infrared-flicker detector IRD 1010
- UV solid state sensor UVD 970
SPECIFICATION
- Part Number TF974, 65320054
- Operating voltage 220 / 240 V (-15... +10%) 50 Hz (40 - 60 Hz)
- Fuse rating 10 A fast, 6 A slow
- Power consumption ca. 5 VA
- Max. current rating
- output terminal: term. 2 0.5 A, cos ϕ 0.4
- output terminal: term. 3 1.5 A, cos ϕ 0.2
- output terminal: term. 4 4 A, cos ϕ 0.4
- output terminal: term. 5 0.5 A, cos ϕ 0.4
- output terminal: term. 6 4 A, cos ϕ 0.4
- output terminal: terml. 8 0.1 A, cos ϕ 0.4
- total: 5 A, cos ϕ 0.4
- Pre-purge time ca. 12 sec.
- Pre-ignition time ca. 12 sec.
- Post-ignition time ca. 20 sec. TF 974
- Lockout safety time10 sec.
- Reset time from lockout ca. 60 sec.
- Flame detector MZ 770 S for side-on and end-on viewing
- Light sensitivity > 6 Lux
- Sensor operating current min. 30 µA
- IRD 1010 for side-on or end-on viewing
- UVD 970 end-on viewing
- Weight incl. wiring base 0,25 kg
- Mounting position any
- Protection class IP 40
- Recommended ambient operating temperature for control and flame detector 0°C... +60°C
- Approval EN 230
Details
What customers say
Do you own or have used the product?
Submit review